CC1 Mini Contactor for 9-12A
Description
Application: remote making & breaking circuits; protect circuit
from over-load when assembling with thermal over-load relay; frequent start-up and control of AC contactor;
Electric value: AC50/60Hz, 690V, up to 12A; Utilization category: AC-3, AC-4;
Altitude: ≤2000m;
Ambient temperature: -5℃~+40℃; Mounting category: Ⅲ;
Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;
Standard: IEC/EN 60947-4-1. IEC/EN 60947-5-1.
Control Coil Voltage(AC Coil Operation)
Volts(VAC) |
24 |
36 |
42 |
48 |
110 |
127 |
220 |
230 |
240 |
380 |
415 |
440 |
480 |
500 |
600 |
|
Code |
50Hz |
B5 |
C5 |
D5 |
E5 |
F5 |
G5 |
M5 |
P5 |
U5 |
Q5 |
N5 |
R5 |
- |
S5 |
Y5 |
60Hz |
B6 |
- |
D6 |
E6 |
F6 |
G6 |
M6 |
- |
U6 |
Q6 |
- |
R6 |
T6 |
- |
- |
|
50/60Hz |
B7 |
- |
D7 |
E7 |
F7 |
- |
M7 |
P7 |
- |
Q7 |
N7 |
R7 |
- |
- |
- |
Control Coil Voltage(DC Coil Operation)
Volts(VDC) |
12 |
24 |
36 |
48 |
110 |
220 |
Code |
JD |
BD |
CD |
ED |
FD |
MD |
Technical Specification
Standard | IEC/EN60947-4-1 IEC/EN60947-5-1 | |||
Model No. |
CC1-06E |
CC1-09K |
CC1-12K |
|
Rated Conventional Heating Current |
Ith (A) |
16 |
20 |
20 |
Rated Voltage Ui(V) |
Ui(V) |
690 |
690 |
690 |
Rated Operation Current
Ue=380/415V |
AC-3 Ie(A) |
6 |
9 |
12 |
AC-4 Ie(A) |
1.5 |
3.5 |
5 |
|
Power Controlled 3ph cage Motor
AC-3 |
220/240V KW |
2.2 |
2.2 |
3 |
380/415V KW |
3 |
4 |
5.5 |
|
660/690V KW |
5.5 |
5.5 |
7.5 |
|
Electrial life(x103 operations) |
AC-3 |
1000 |
1000 |
1000 |
AC-4 |
200 |
200 |
200 |
|
Mechanical life(x106 operations)) |
10 |
10 |
10 |
|
Matched Fuse |
Size |
RT16-00 |
RT16-00 |
RT16-00 |
A |
20 |
20 |
20 |
|
Main circuit |
3P or 4P |
|||
Auxiliary circuit Cat.:AC-15,Ue=415V Ie=0.95A Ith=10A |
1NO or 1NC |